1100 Litre Slimline Fire Protected Steel Bunded Oil Tank - Tuffa 1100SBFP

Gauge & Outlet Kit inc.FREE Delivery*
FREE Delivery (Customer To Offload) | HIAB Available | Lead Time Varies: Please enquire
TuffaSKU: 1100SBFP

Price:
£3,225.00 exc. VAT
(
Sale price£3,870.00

Tax included

)

Description

Tuffa 1100 Litre Steel Bunded Slimline Fire Protected Oil Storage Tank

The 1100 Litre Steel Bunded Fire Protected Oil tank is our slimline model manufactured in an extremely durable mild steel. The integral fire protection barrier protects the contents of the tank, providing a 30 or 60 minute fire rated barrier enabling tank installation adjacent to or even inside buildings. Designed to be neatly hidden away in narrow installations, this oil tank can hold up to 1100 litres (240 gallons) of heating oil and HVO compatible. 

The integrally fire rated system meets the functional requirements of Building Regulations and can be installed and signed off under Competent Persons schemes such as APHC. With a fitted bund, the tank also provides protection against any leakage or spills.

Specifications:

  • Fire protection
  • 2″ BSP fill connection with cap and chain
  • Overfill prevention valve
  • Vent
  • Manual float level gauge
  • Electronic Watchman Sonic gauge
  • Lockable flip lid
  • 1″ bottom outlet
  • Tank fittings kit (1”-1/2″ adaptor, ball valve and filter)

 Tank Dimensions:

  • Length: 2200mm
  • Width: 675mm
  • Height: 1500mm
  • Weight: 570kg
Fire Protection Requirements 

Domestic:

  • 30 minute fire protection – install a domestic tank adjacent to buildings and boundaries
  • 60 minute fire protection – install a domestic tank inside an uninhabited building such as a garage (pending installer/inspector approval)

Non-domestic:

  • 60 minute fire protection – install a non-domestic tank adjacent to buildings and boundaries
Benefits of Tuffa Fire Protected Oil Storage Tanks
  • Enables you to save valuable outside space and hide your tank away behind or even inside outbuildings
  • Offers a perfect solution to replace old tanks which are sited within 1.8m of buildings and structures and are incompliant with modern regulations
  • Great alternative form of compliance to constructed fire barriers without the need for additional building work
  • All of our fire protected tanks are bunded offering integral protection from leakage and overfilling
Installation Requirements

Tuffa’s fire protected oil tanks serve as an alternative means of compliance when compared to traditional fire barriers. It is the responsibility of the Competent Person installing the tank, or the building inspector certifying the installation, to ensure a site-specific risk assessment has been conducted.  

30 minute fire protection   Enables the installation of an oil tank a minimum of 300mm from other buildings and structures. Where access is required (e.g. at the front of the tank to fill it) then a minimum distance of 600mm is required.  

60 minute fire protection   Enables the installation of an oil tank within a garage or other internal space where it is impractical to install the tank externally to the building. The tank must be installed in an uninhabitable area (e.g. a garage or outbuilding), at the lowest possible level in the building or structure. Additionally, the tank must be installed a minimum of 300mm from other internal walls and structures or 600mm where access is required